Product Name: Air cooling modular chiller
Model: FAC-100
Supply for:
* Emailú║
* Messageú║
* Required information
Detailed Product Description

Air cooling modular chiller (Heating and cooling)

 Model

heatpump

FAC-25

FAC-50

FAC-75

FAC-100

FAC-125

unit functions

rated coolig

rated cooling capacity 

kW

66.2

132.4

198.6

264.8

331

Btu/h

225939 

451877 

677816 

903754 

1129693 

Rated cooling input power

kW

22.4

44.8

67.2

89.6

112

rated cooling input current

A

41

82

123

164

205

rated heating

heating capacity

kW

70.8

141.6

212.4

283.2

354

Btu/h

241638 

483276 

724915 

966553 

1208191 

input power

kW

22

44

66

88

110

input current

A

40

80

120

160

200

max ruuning current

A

54

108

162

216

270

power

V/Ph/Hz

380V/3N/50Hz

noise

dB(A)

68

71

74

77

79

size

L(A)

mm

2205

2205

2205

2205

2205

w(B)

mm

1110

2140

3170

4200

5230

H(C)

mm

2090

2090

2090

2090

2090

WEIGHT

kg

920

1840

2760

3680

4600

operating control

precision temp precision

íŠ

í└1íŠ

operation range

íŠ

í¬20íŠíź45íŠ

operation panel

type

 

 LCD

main functions

 

operating modeíótemperature setingíóoperating conditioníótiming

number of compressor 

pc

4

8

12

16

8

range of capacity regulation

%

multilevel

Throttling

 

 capillary/thermostatic expansion valve

refrigerate

type

 

R407C,R417A

refrigerant charge

kg

4.5*4

4.5*8

4.5*12

4.5*16

4.5*20

Compressor

type

 

sanyo,copeland

security function

 

Built-in protection device overheating protection, sequence protection, undervoltage protection, delay protect

air side heat exchange

type

 

finned heat exchange

fan type

 

axial big twist angle fan

use side heat exchange

type

 

plate heat exchanger

water flow(summer)

m3/h

11.38

22.77

34.15

45.54

56.92

water flow(winter)

m3/h

12.18

24.35

36.53

48.7

60.88

water pressure down

kpa

30-70

connection dimension

inch

4

4

4

5

5

water side max working pressure

KPA

1200

Rated cooling working conditions: air side return air temp 35íŠ, use side input water temp is 12íŠ, outlet water temp is 7íŠ
Rated heating working conditions: air side return air dry ball temp is 7
íŠ, wet ball temp is 6íŠ, use side input water temp 40íŠ, outlet water temp is 45íŠ